Low smoke, Halogen free fire resistant cableLow
smoke, Halogen free fire resistant cable. This
cable has been tested and approved by the Loss
Prevention Certification board and approved to
BS6387 Categories C,W and Z.APPLICATIONSThis
cable is an ideal for Fire detection systems,
emergency lighting and public address
systems.FEATURESHigh mechanical strengthZero
halogen, low smoke & fumeScreened against
electrostatic interferenceFlame retardant
jacket.
TECHNICAL DATA
Voltage Rating: 300/500 volts
Operating Temperature: -20°C to +70°C
Resistance to fire alone: BS 6387 Cat. C, 950°C
for 3 hours IEC 331, 750°C for 3 hours.
Resistance to fire with water spray: BS 6387
Cat. W, 15 mins at 650°C followed by fire and
water spray for 15 minutes.
Resistance to fire with mechanical shock: BS
6387 Cat. Z, 950°C with applied mechanical
shock for 15 minutes.
|